Nidec Readies 6.4 MW Twin CDU Skid; NIR 3.0 Rated 3.2 MW at 3°C
Nidec says its NIR 3.0 CDU hits a 3°C approach at 3.2 MW, with a 6.4 MW skid. By our math, 14 Vera Rubin racks; no price, ship date or customer given.
2 min read

Nidec's NIR 3.0 figures are vendor claims; the company aims for mass production in H1 2027.
Graphic: Voltgrid News
Nidec is preparing a 3.2 MW in-row coolant distribution unit (CDU) and a 6.4 MW twin-unit skid, Nobuyasu Nozawa, deputy head of its AI & IT Division SPMS, told DataCenterNews Asia Pacific on Nov. 27.
Nozawa said the unit, called NIR 3.0, reaches a 3°C approach temperature at a 3,200 kW load, against the 4-5°C he described as typical of current systems. The approach is the gap between the facility water and the coolant sent to the racks. He said the front of the chassis gives access to key components, the unit can monitor coolant quality, and it accepts 800 V DC as well as 415 V AC power. Nidec said it is also designing more parts in-house, such as the pumps, and that it has shipped more than 13,000 CDUs, with North America the largest market and Southeast Asia second.
Nidec's own pages put dates and limits on that. Its Oct. 14 press release called NIR3.0 a prototype shown at the OCP Global Summit and said Nidec aims to begin mass production in the first half of 2027. Its in-row CDU page, read on Nov. 27, marks the 800 V DC input as an option "currently under evaluation" and lists a harmonic distortion (THDi) of 5% or less and group control of up to 10 CDUs.
How 3.2 MW compares with other CDUs
All ratings here are the makers' own and use their own conditions. CoolIT's CHx 3000 is rated 3 MW at a 3°C approach, Trane's LiquidStack-built unit up to 2.5 MW at 4°C, and nVent's CX121 2.3 MW. Nidec's figure is 6.7% above CoolIT's by our arithmetic, at the same 3°C approach. Nidec's own NIR 2.5 is listed at up to 2 MW and as supporting NVIDIA Vera Rubin NVL72 racks.
Nidec's NIR 3.0 is rated 3.2 MW, above CoolIT's 3 MW; all are makers' own claims, with no independent test.
Graphic: Voltgrid News
NVIDIA's Vera Rubin datasheet lists 227 kW per NVL72 rack at its highest power setting, MaxP, and 156 kW at MaxLPS. By our arithmetic, 3,200 kW divided by 227 kW is 14.1 racks, or 20.5 at 156 kW, and the 6.4 MW skid covers 28.2 racks at 227 kW. The same division gives 13.2 racks for CoolIT, 11.0 for Trane and 10.1 for nVent. That counts all rack power as heat to the liquid and ignores redundancy, flow and pressure limits, and Nidec states no rack count of its own.
On supply, Schneider Electric said it will double CDU output at its Italian plant from January 2027. Nidec names Thailand as its central CDU manufacturing hub, but gave no output figure for it.
What is not confirmed yet
The interview gives no ship date, price or named customer for NIR 3.0, and Nidec's press release is the only source for the first-half 2027 production aim. Nidec has not said whether 3.2 MW counts heat removed or electrical load, or at what facility water temperature. Its in-row page cites factory tests at a 750 kW thermal load and 3,750 LPM flow, with a rise to 1,500 kW planned, and does not say whether NIR 3.0 has run at 3.2 MW. The 13,000 figure covers all CDUs in the interview, while Nidec's site counts in-rack units. No independent test of either rating has been published.